MODEL
|
LCM-40DA
|
OUTPUT
|
SELECTABLE CURRENT Note.3
|
350mA
|
500mA
|
600mA
|
700mA
|
900mA
|
1050mA
|
DC VOLTAGE
|
2 ~ 100V
|
2 ~ 80V
|
2 ~ 67V
|
2 ~ 57V
|
2 ~ 45V
|
2 ~ 40V
|
RATED POWER
|
42W
|
RIPPLE CURRENT
|
plus/minus 5%
|
RIPPLE & NOISE (max.) Note.2
|
700mVp-p
|
NO LOAD OUTPUT VOLTAGE (max.)
|
110V
|
65V
|
CURRENT ACCURACY
|
plus/minus 5%
|
SETUP, RISE TIME Note.5
|
1000ms, 80ms / 230VAC at rated power
|
HOLD UP TIME (Typ.)
|
16ms/230VAC at rated power
|
INPUT
|
VOLTAGE RANGE Note.4
|
180 ~ 295VAC 254 ~ 417VDC
|
FREQUENCY RANGE
|
47~63Hz
|
POWER FACTOR
|
PF≥0.975/230VAC, PF≥0.96/277VAC at rated power (Please refer to "Power Factor Characteristic" section)
|
TOTAL HARMONIC DISTORTION
|
Total harmonic distortion will be lower than 20% when output loading is 75% or higher
|
EFFICIENCY (Typ.)
|
91%
|
AC CURRENT
|
0.23A/230VAC 0.2A/277VAC
|
INRUSH CURRENT (Typ.)
|
COLD START 20A (twidth=260us measured at 50% Ipeak) at 230VAC
|
LEAKAGE CURRENT
|
<0.5mA / 240VAC
|
PROTECTION
|
SHORT CIRCUIT
|
Constant current limiting, recovers automatically after fault condition is removed
|
OVER VOLTAGE
|
110 ~ 130V
|
Protection type : Shutdown o/p voltage, re-power on to recover
|
OVER TEMPERATURE
|
90celsius degrees plus/minus 10 celsius degree(RTH2)
|
Protection type : Shut down o/p voltage, re-power on to recover
|
FUNCTION
|
AUXILIARY POWER
|
12V @ 50mA for driving fan; Tolerance plus/minus 5%
|
TEMP. COMPENSATION
|
By external NTC(not provide with the power supply), please see "Temperature compensation operation"
|
DIMMING
|
Please refer to "Dimming Operation" section
|
SYNCHRONIZATION
|
Please refer to "Synchronization Operation" section
|
ENVIRONMENT
|
WORKING TEMP.
|
-30 ~ +60celsius degree (Refer to "Derating Curve")
|
WORKING HUMIDITY
|
20 ~ 95% RH non-condensing
|
STORAGE TEMP., HUMIDITY
|
-40 ~ +80,10~95% RH
|
TEMP. COEFFICIENT
|
plus/minus 0.03%/ celsius degree (0 ~ 50celsius degree)
|
VIBRATION
|
10 ~ 500Hz, 5G 12min./1cycle, period for 60min.each along X, Y,Z axes
|
SAFETY & EMC
|
SAFETY STANDARDS
|
UL8750, ENEC EN61347-1, EN61347-2-13,EN62384 independent approved
|
DALI STANDARDS
|
Comply with IEC62386-101, 102, 207
|
WITHSTAND VOLTAGE
|
I/P-O/P:3.75KVAC
|
ISOLATION RESISTANCE
|
I/P-O/P:>100M Ohms / 500VDC / 25 celsius degree / 70% RH
|
EMC EMISSION
|
Compliance to EN55015, EN61000-3-2 Class C(≥40% rated power) ; EN61000-3-3
|
EMC IMMUNITY
|
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61547 light industry level (surge 2KV), criteria A
|
OTHERS
|
MTBF
|
193.6K hrs min. MIL-HDBK-217F (25celsius degree)
|
DIMENSION
|
123.5*81.5*23mm (L*W*H)
|
PACKING
|
0.24Kg ; 54pcs/15Kg/1.12CUFT
|
NOTE
|
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 celsius degree of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Please refer to "DIP Switch Table" section.
4. Derating may be needed under low input voltages. Please check the static characteristics for more details.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. Efficiency is measured at 500mA/80V output set by DIP switch.
7. No load power consumption<1.2W is measured at 180 277VAC, with lighting fixture connected and output current dimmed to 0%.